2. How to Programme
2.1. The Graphical and Numerical Local Control Panels
The easiest programming of the frequency converter is performed by the Graphical Local Control Panel (LCP 102). It is necessary to consult the frequency
converter Design Guide, when using the Numeric Local Control Panel (LCP 101).
2.1.1. How to Programme on the Graphical LCP
The following instructions are valid for the graphical LCP (LCP 102):
The control panel is divided into four functional groups:
1.
Graphical display with Status lines.
2.
Menu keys and indicator lights - changing parameters and
switching between display functions.
3.
Navigation keys and indicator lights (LEDs).
4.
Operation keys and indicator lights (LEDs).
All data is displayed in a graphical LCP display, which can show up to five
items of operating data while displaying [Status].
Display lines:
a.
Status line:
Status messages displaying icons and graphic.1
b.
Line 1-2:
Operator data lines displaying data defined or chosen
by the user. By pressing the [Status] key, up to one extra line
can be added.1
c.
Status line:
Status messages displaying text.1
2.1.2. The LCD-Display
The LCD-display has back light and a total of 6 alpha-numeric lines. The display lines show the direction of rotation (arrow), the chosen Set-up as well
as the programming Set-up. The display is divided into 3 sections:
Top section
shows up to 2 measurements in normal operating status.
The top line in the
Middle section
shows up to 5 measurements with
related unit, regardless of status (except in the case of alarm/warning).
Bottom section
always shows the state of the frequency converter in
Status mode.
130BP074.10
Top section
Middle section
Bottom section
The Active Set-up (selected as the Active Set-up in par. 0-10) is shown. When programming another Set-up than the Active Set-up, the number of the
programmed Set-up appears to the right.
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark