[Reset]
is used for resetting the frequency converter after an alarm (trip). It can be selected as Enable [1] or Disable [0] via par. 0-43
Reset Keys on
LCP
.
2.1.19. Initialisation to Default Settings
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22)
1.
Select par. 14-22
2.
Press [OK]
3.
Select “Initialisation”
4.
Press [OK]
5.
Cut off the mains supply and wait until the display turns off.
6.
Reconnect the mains supply - the frequency converter is now
reset.
Par. 14-22 initialises all except:
14-50
RFI 1
8-30
Protocol
8-31
Address
8-32
Baud Rate
8-35
Minimum Response Delay
8-36
Max Response Delay
8-37
Max Inter-char Delay
15-00 to 15-05
Operating data
15-20 to 15-22
Historic log
15-30 to 15-32
Fault log
Manual initialisation
1.
Disconnect from mains and wait until the dis-
play turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the
same time while power up for LCP 102, Graph-
ical Display
2b.
Press [Menu] while power up for LCP 101, Nu-
merical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This parameter initialises all except:
15-00
Operating Hours
15-03
Power-up's
15-04
Over temp's
15-05
Over volt's
NB!
When you carry out manual initialisation, you also reset serial communication, RFI filter settings (par. 14-50) and fault log settings.