[23]
Set-up select bit 0
Select Set-up select bit 0 or Select Set-up select bit 1 to select one of the four set-ups. Set par. 0-10
Active Set-
up
to Multi Set-up.
[24]
Set-up select bit 1
(Default Digital input 32): Same as Set-up select bit 0 [23].
[26]
Precise stop inv.
Prolongs stop signal to give a precise stop independent of speed.
Sends an inverted stop signal when the precise stop function is activated in par. 1-83
Precise Stop Function
.
Precise stop inverse function is available for terminals 18 or 19.
[27]
Precise start, stop
Use when Precise ramp stop [0] is selected in par 1-83
Precise stop function
.
[28]
Catch up
Increases reference value by percentage (relative) set in par. 3-12.
[29]
Slow down
Reduces reference value by percentage (relative) set in par. 3-12.
[30]
Counter input
Precise stop function in par. 1-83 acts as Counter stop or speed compensated counter stop with or without reset.
The counter value must be set in par. 1-84.
[32]
Pulse input
Use pulse sequence as either reference or feedback. Scaling is done in par. group 5-5*.
[34]
Ramp bit 0
Enables a choice between one of the 4 ramps available, according to the table below.
[35]
Ramp bit 1
Same as Ramp bit 0.
Preset ramp bit
1
0
Ramp 1
0
0
Ramp 2
0
1
Ramp 3
1
0
Ramp 4
1
1
[36]
Mains failure inverse
Activates par. 14-10
Mains Failure
. Mains failure inverse is active in the Logic .0. situation.
[41]
Latched Precise Stop
inverse
Sends a latched stop signal when the precise stop function is activated in par. 1-83
Precise Stop Function
. The
Latched Precise stop inverse function is available for terminals 18 or 19.
[55]
DigiPot Increase
INCREASE signal to the Digital Potentiometer function described in parameter group 3-9*
[56]
DigiPot Decrease
DECREASE signal to the Digital Potentiometer function described in parameter group 3-9*
[57]
DigiPot Clear
Clears the Digital Potentiometer reference described in parameter group 3-9*
[60]
Counter A
(Terminal 29 or 33 only) Input for increment counting in the SLC counter.
[61]
Counter A
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
[62]
Reset Counter A
Input for reset of counter A.
[63]
Counter B
(Terminal 29 or 33 only) Input for increment counting in the SLC counter.
[64]
Counter B
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
[65]
Reset Counter B
Input for reset of counter B.
[70]
Mech. Brake Feedback Brake feedback for hoisting applications
[71]
Mech. Brake Feedback
inv.
Inverted brake feedback for hoisting applications
[80]
PTC Card 1
All Digital Inputs can be set to PTC Card 1 [80]. However, only one Digital Input must be set to this choice.
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®