2.8. Parameters: Digital In/Out
2.8.1. 5-** Digital In/Out
Parameter group for configuring the digital input and output.
2.8.2. 5-0* Digital I/O Mode
Parameters for configuring the IO mode. NPN/PNP and setting up IO to Input or Output.
5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital outputs are pre-programmable for operation either in PNP or NPN systems.
[0]
*
PNP
Action on positive directional pulses
(↕)
. PNP systems are pulled down to GND.
[1]
NPN
Action on negative directional pulses
(↕)
. NPN systems are pulled up to + 24 V, internally in the frequency
converter.
NB!
When changing this parameter, a power cycle must be carried out before the parameter change is active.
This parameter cannot be adjusted while the motor is running.
5-01 Terminal 27 Mode
Option:
Function:
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
This parameter cannot be adjusted while the motor is running.
5-02 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
This parameter is available for FC 302 only.
This parameter cannot be adjusted while the motor is running.
2.8.3. 5-1* Digital Inputs
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the following functions:
2. How to Programme
FC 300 Programming Guide
80
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark