8-55 Set-up Select
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the fieldbus.
[0]
Digital input
[1]
Bus
Activates the set-up selection via the serial communication port or fieldbus option.
[2]
Logic AND
Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one of
the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Select control of the frequency converter Preset Reference selection via the terminals (digital input) and/or via the
fieldbus.
[0]
Digital input
[1]
Bus
Activates Preset Reference selection via the serial communication port or fieldbus option.
[2]
Logic AND
Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally via
one of the digital inputs.
[3]
*
Logic OR
Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of the
digital inputs.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
2.11.6. 8-9* Bus Jog
Parameters for configuring the Bus Jog.
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
*
[0 - par. 4-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM
*
[0 - par. 4-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
2.12. Parameters: Profibus
2.12.1. 9-** Profibus
Parameter group for all Profibus-specific parameters.
9-00 Setpoint
Range:
Function:
0
*
[0-65535]
This parameter receives cyclical reference from a Master Class 2. If the control priority is set to Master Class 2,
the reference for the frequency converter is taken from this parameter, whereas the cyclical reference will be
ignored.
2. How to Programme
FC 300 Programming Guide
110
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
2