5-65 Pulse Output Maximum Frequency #29
Option:
Function:
[5000Hz]
*
0 - 32000 Hz
Set the maximum frequency for terminal 29 corresponding to the output variable set in par. 5-63.
This parameter cannot be adjusted while the motor is running.
5-66 Terminal X30/6 Pulse Output Variable
Option:
Function:
[0]
*
No operation
Select the variable for read-out on terminal X30/6. This parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is installed in the frequency converter.
5-68 Pulse Output Maximum Frequency #X30/6
Range:
Function:
5000Hz
*
[0 - 32000 Hz]
Select the maximum frequency on terminal X30/6 referring to the output variable in par. 5-66. This parameter
cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is mounted in the frequency converter.
2.8.8. 5-7* 24 V Encoder Input
Parameters for configuring the 24 V encoder.
Connect the 24 V encoder to terminal 12 (24 V DC supply), terminal 32 (Channel A), terminal 33 (Channel B), and terminal 20 (GND). The digital inputs
32/33 are active for encoder inputs when
24 V encoder
is selected in par. 1-02 and par. 7-00. The encoder used is a dual channel (A and B) 24 V type.
Max input frequency: 110 kHz.
5-70 Term 32/33 Pulses per Revolution
Range:
Function:
1024PPR
*
[128 - 4096 PPR]
Set the encoder pulses per revolution on the motor shaft. Read the correct value from the encoder.
This parameter cannot be adjusted while the motor is running.