4-31 Motor Feedback Speed Error
Range:
Function:
300 RPM
*
[1-600 RPM]
Select the max allowed tracking error in speed from the calculated and the actual mechanical shaft output speed.
4-32 Motor Feedback Loss Timeout
Range:
Function:
0.05 s
*
[0.00 - 60.00 sec]
Set the timeout value allowing the speed error set in par. 4-31 to be exceeded.
2.7.4. 4-5* Adjustable Warnings
Define adjustable warning limits for current, speed, reference and feedback. Warnings are shown on the display, programmed output or serial bus.
Warnings are shown on display, programmed output or serial bus.
4-50 Warning Current Low
Range:
Function:
0.00 A
*
[0.00 - par. 4-51]
Enter the I
LOW
value. When the motor current falls below this limit, the display reads
Current Low
. The signal
outputs can be programmed to produce a status signal on terminal 27 or 29 (FC 302 only) and on relay output
01 or 02 (FC 302 only). Refer to the drawing in this section.
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
77