The par. 0-12 link set-up feature is used by Multi set-up in par. 0-10
Active Set-up
. Multi set-up is used to move
from one set-up to another during operation (i.e. while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 whilst the motor is running. Programme in Set-up 1 first,
then ensure that Set-up 1 and Set-up 2 are synchronised (or ‘linked’). Synchronisation can be performed in two
ways:
1. Change the edit set-up to
Set-up 2
[2] in par. 0-11
Edit Set-up
and set par. 0-12
This Set-up Linked to
to
Set-up 1
[1]. This will start the linking (synchronising) process.
130BP075.10
OR
2. While still in Set-up 1, copy Set-up 1 to Set-up 2. Then set par. 0-12 to
Set-up 2
[2]. This will start the linking
process.
130BP076.10
After the link is complete, par. 0-13
Readout: Linked Set-ups
will read {1,2} to indicate that all ‘not changeable
during operation’ parameters are now the same in Set-up 1 and Set-up 2. If there are changes to a ‘not change-
able during operation’ parameter, e.g. par 1-30
Stator Resistance (R
s
)
, in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between Set-up 1 and Set-up 2 during operation is now possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4