2-9
2.3 Set point of functional parts and protection devices
Initiation
Pressure
switch
Device name
Actuation
Set point
Detection method
Symbol
High-pressure switch
OFF
2400kPa (24.47kg/cm
2
)
High-pressure switch
HPS
ON
1900kPa (19.37kg/cm
2
)
Water pressure switch
OFF
98kPa (1.0kg/cm
2
)
Water pressure switch
WPS
ON
39kPa (0.4kg/cm
2
)
Chilled mode
ON
+30.0°C to –5.0°C
Set point temperature
EC
(+86.0°F to –41.0°F)
Mode selection Frozen mode
–5.1°C to –30.0°C
(–41.2°F to –22.0°F)
Delay
Fan
Change-over for Hi/Lo
ON
10 seconds
timer
After defrosting
60 seconds
Compressor At starting
3 seconds
Defrosting
Short
ON
4 hours
※
1
timer
Long
3, 6, 9, 12, 24 and 99 hours(
※
2)
Back-up
OFF
90 minutes
In-range masking
90 minutes
※
3
Out-range guard
ON
30 minutes
Defrosting termination set point
OFF
30˚C (86°F)
Evaporator outlet
EOS
Reset
tempertature sensor
15˚C (59°F)
※
4
Return air temperature
RS, DRS
sensor
High-pressure control for Condenser fan
OFF
800kPa (8.2kg/cm
2
)
※
6
High-pressure transducer
HPT
(※
Frozen only)
ON
1000kPa (10.2kg/cm
2
)
Condenser fan ON/OFF setting value
OFF
49˚C (120.2°F)
Control box sensor
CBS
ON
59˚C (138.2°F)
Discharge gas
Pull down
OFF
135˚C (275°F)
Discharge gas
DCHS
temperature
LPT>50kpa
Reset
After 3 minutes elapsed
temperature sensor
protection
LPT
≦
50kpa
OFF
128˚C (262°F)
set point
Reset
After 3 minutes elapsed
Overcurrent protection set point (Cutout)
OFF
26.0A
PT/CT board
CT2
Reset
After 3 minutes elapsed
Current control
Control
50Hz : 16.1A
PT/CT board
CT1
60Hz : 17.4A
High pressure control
Control
2300 to 2350 kPa
High pressure sensor
HPT
(23.5 to 24.0 kg/cm
2
)
Circuit breaker
OFF
30A
CB
Fuse
OFF
5A, 10A
※
5
Fu
Evaporator fan motor thermal protector
OFF
132˚C (270°F)
Condenser fan motor thermal protector
OFF
135˚C (275°F)
MTP
Compressor motor thermal protector
OFF
140˚C (284°F)
CTP
Fusible plug
−
95
〜
100˚C
Electronic
controller
Current
Motor
−
(
※
1) When Return air (RS) is lower than –20˚C, defrost starts every 6 hours.
(
※
2) When "99" hours is selected, refer to on demand defrost in 2.5.3.
(
※
3) When Inside set point is –20.0˚C or Lower, In-range masking is 120min.
(
※
4) If defrost is initiated when inside temperature is out rangle area. (= In-range LED is not light), this condition is added to
finish defrost. Refer to "Defrosting termination" in 2.5.3.
(
※
5) Refer to "Fuse Protection table" in 7.13.
(
※
6) When dehumidification is ON in dehumidification mode, the setting figure may change between 900~2100kPa
automatically (Refer to "High Pressure Control" Page 2-24).