7-1
7. APPENDIX
7.1 Standard tightening torques for bolts
Bolt size
Main part
Tightening torque
N
m
kgf
cm
lbf
ft
M4
Small parts
1.6
16
1.2
M5
Solenoid valve
3.0
31
2.2
M6
Access panel
5.2
53
3.8
Evaporator fan motor
M8
Condenser fan motor
12.3
125
9.1
Control box
Service door
Evaporator fan motor mounting base
M10
Compressor suction flange
25.2
257
18.6
Compressor discharge flange
M12
Compressor
42.7
435
31.5
Note: Tolerance of tightening torque is within ±10%.
Note: Tolerance of tightening torque is within ± 10%.
Stainless
s
teel
7.2 Standard tightening torque for flare nut
Pipe size
Main part
Tighten torque
mm
in.
N
m
kgf
cm
Ibf
ft
φ
6.4
2/8
Compressor pressure port
15.7
160
11.3
φ
9.5
3/8
–
36.3
370
26.8
φ
12.7
4/8
Only Dryer
28.0
286
20.7
Note: Tolerance of tightening torque is within ± 10%.
Suction side stop valve
N · m
kg · cm
Ibf · ft
Backseat torque
35
357
25.8
Grand torque
15
153
11.8
7.3 Standard tightening torque for stop valve
Discharge side stop valve
N · m
kg · cm
Ibf · ft
20
204
14.8
15
153
11.8
φ
12.7
4/8
Except Dryer
54.9
500
40.5
https://daikin-p.ru