3-60
3.10.3 Chartless code display function
The chartless code represents the coded inside air temperature.
Select "ON" of the chartless code setting to indicate the code on the LED.
For the chartless code setting, refer to the "optional conditions setting" on the page 3-29.
P code: Indicates the pull-down time.
H code: Indicates the abnormal temperature records.
d code: Indicates the operation history.
3.10.3.1 List of chartless code
C: chilled mode, F: Frozen mode, PF: Partial frozen mode
Note 1) The encircled setting can be changed.
Note 2) To delete the H code or d code, press the
key for 3 seconds during the
relevant code indicated.
Note 3) H code and d code are deleted when turn off the power supply for 3 days.
Code
Description
Operation mode Figure
Abnormal
temperature
record
H001
The alarm is displayed when the control temperature does not decrease by
3˚C or more for every 4 hours during pull-down operation.
C, F, PF
2
H002
The alarm is displayed when the total out-of- in-range reaches 2 hours.
(Count is not performed during defrosting.)
C, F, PF
3
H003
The alarm is displayed when the integrated time of state "below SP-1˚C"
reaches 2 hours.
C
4
H004
The alarm is displayed when the integrated time of state "below SP-2˚C"
reaches 2 hours.
C
4
H005
The alarm is displayed when the control air temperature is Out-of -In-
Range and defrosting was performed successively three times while the
control air temperature does not return to in-range.
C, F, PF
5
H006
The alarm is displayed when the integrated time of difference 2 ˚C or more
between control sensor data and record sensor data reaches to one hour
or more.
C, F, PF
6
Opreration
history
d3XX
When the total time above set point +3˚C reaches 1 hour , the code
"d301" will be displayed.
C, F, PF
7
d2XX
When the total time above set point +2˚C reaches 1 hour , the code
"d201" will be displayed.
C, F, PF
7
d1XX
When the total time above set point +1˚C reaches 1 hour , the code
"d101" will be displayed.
C, F, PF
7
d–1X
When the total time below set point –1˚C reaches 1 hour , the code
"d-11" will be displayed.
C, F, PF
7
d–2X
When the total time below set point –2˚C reaches 1 hour , the code
"d-21" will be displayed.
C, F, PF
7
PXXX
XXX: When the total pull-down time reaches one hour, an indication
XXX=001 appears.
C, F, PF
1