Pressure
Out put
(kPa
G)
(V)
– 500
– 1.03
– 400
– 0.72
– 300
– 0.42
– 200
– 0.11
– 100
0.19
0
0.50
100
0.81
200
1.11
300
1.42
400
1.72
500
2.03
600
2.34
700
2.64
800
2.95
900
3.25
1000
3.56
7-5
7.8 Temperature sensor characteristics table (DCHS)
Temperature(
°
C)
Temperature(
°
F)
Resistance(k
Ω
) Temperature(
°
C)
Temperature(
°
F)
Resistance(k
Ω
)
72
162
32.783
102
216
12.566
74
165
30.629
104
219
11.835
76
169
28.635
106
223
11.153
78
172
26.787
108
226
10.515
80
176
25.073
110
230
9.919
82
180
23.482
112
234
9.361
84
183
22.005
114
237
8.840
86
187
20.633
116
241
8.351
88
190
19.358
118
244
7.894
90
194
18.171
120
248
7.465
92
198
17.066
122
252
7.063
94
201
16.037
124
255
6.685
96
205
15.078
126
258
6.331
98
208
14.184
128
262
5.998
100
212
13.350
130
266
5.686
7.9 High pressure transducer
characteristics table
Pressure
Out put
Pressure
Out put
(kPa
G)
(V)
(kPa
G)
(V)
0
0.50
1100
1.62
100
0.60
1200
1.72
200
0.70
1300
1.83
300
0.81
1400
1.93
400
0.91
1500
2.03
500
1.01
1600
2.13
600
1.11
1700
2.23
700
1.21
1800
2.34
800
1.32
1900
2.44
900
1.42
2000
2.54
1000
1.52
2100
2.64
7.10 Low pressure transducer
characteristics table
https://daikin-p.ru
Содержание LXE10E-1
Страница 161: ...7 9 https daikin p ru ...
Страница 162: ...7 14 Schematic wiring diagram LXE10E 1 7 10 https daikin p ru ...
Страница 163: ...7 15 Stereoscopic wiring diagram LXE10E 1 7 11 https daikin p ru ...