ESIE09-05
Troubleshooting by Remote Controller
Troubleshooting
159
w
: ON
x
: OFF
c
: Blink
Malfunction
code
Operation
lamp
Malfunction contents
Page
Referred
AHU
A0
c
Error of external protection device
A1
c
PC board defect, E
2
PROM defect
A3
c
Malfunction of drain level control system (S1L)
—
A6
c
Fan motor (M1F) lock, overload
A8
c
Abnormal power supply voltage
A9
c
Malfunction of moving part of electronic expansion valve (Y1E)
AF
w
Drain level above limit
—
AJ
c
Malfunction of capacity setting
C1
c
Failure of transmission (between AHU PC board and fan PC board)
C4
c
Malfunction of thermistor (R2T) for heat exchange (loose connection,
disconnection, short circuit, failure)
C5
c
Malfunction of thermistor (R3T) for gas pipes (loose connection,
disconnection, short circuit, failure)
C6
c
Failure of combination (between AHU PC board and fan PC board)
C9
c
Malfunction of thermistor (R1T) for suction air (loose connection,
disconnection, short circuit, failure)
CA
c
Malfunction of thermistor for discharge air (loose connection,
disconnection, short circuit, failure)
CC
w
Malfunction of humidity sensor system
CJ
w
Malfunction of thermostat sensor in remote controller
Outdoor Unit
E1
c
PC board defect
E3
c
Actuation of high pressure switch
E4
c
Actuation of low pressure sensor
E5
c
Compressor motor lock
E6
c
Standard compressor lock or over current
—
E7
c
Malfunction of outdoor unit fan motor
E9
c
Malfunction of moving part of electronic expansion valve (Y1E, Y3E)
F3
c
Abnormal discharge pipe temperature
F6
c
Refrigerant overcharged
H3
w
Failure of high pressure switch
—
H4
c
Actuation of low pressure switch
—
H7
c
Abnormal outdoor fan motor signal
—
H9
c
Malfunction of thermistor (R1T) for outdoor air (loose connection,
disconnection, short circuit, failure)
J2
c
Current sensor malfunction
—
J3
c
Malfunction of discharge pipe thermistor (R2T) (loose connection,
disconnection, short circuit, failure)
J5
c
Malfunction of thermistor (R3T, R5T) for suction pipe (loose connection,
disconnection, short circuit, failure)
J6
c
Malfunction of thermistor (R6T) for heat exchanger (loose connection,
disconnection, short circuit, failure)
J7
c
Malfunction of thermistor (R7T) for outdoor unit liquid pipe
J9
c
Malfunction of subcooling heat exchanger gas pipe thermistor (R4T)
JA
c
Malfunction of high pressure sensor
JC
c
Malfunction of low pressure sensor
L0
c
Inverter system error
—
L1
c
Malfunction of PC board
L4
c
Malfunction of inverter radiating fin temperature rise
L5
c
Inverter compressor abnormal
L8
c
Inverter current abnormal
L9
c
Inverter start up error
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...