ESIE09-05
Field Setting
Test Operation
101
Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
(Factory setting)
There are the following three setting modes.
c
Setting mode 1 (H1P off)
Initial status (when normal) : Also indicates during “abnormal”.
d
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
e
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Caution
Capacity Setting after changing the main PC Board(A1P) to spare parts PC Board
When you change the main PC Board(A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adaptor corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adaptor
1
2
3
Capacity Class
112
140
160
Outdoor unit
100
125
140
CAPACITY SETTING ADAPTOR (for 100/J112)
CAPACITY SETTING ADAPTOR (for 125/J140)
CAPACITY SETTING ADAPTOR (for 140/J160)
Position of Attaching the Capacity Setting Adaptor
ERQ100 / 125 / 140A7V1B
Note
X51A
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED indication
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
(V2760)
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...