ESIE09-05
Troubleshooting by Remote Controller
Troubleshooting
163
<Selection of setting item>
<Monitor mode>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
Detail
description
on next
page.
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Contents of malfunction
Malfunction
code
Open phase/Power supply imbalance
Imbalance of inverter power supply
voltage
P1
Faulty temperature sensor of inverter
radiation fin
Faulty thermistor of inverter fin
P4
Refrigerant shortage
Refrigerant shortage alarm
U0
Abnormal power supply voltage
Insufficient Inverter voltage
U2
Faulty charge of capacitor in main inverter circuit
Malfunction due to SP-PAM overvoltage
Malfunction due to P-N short circuit
No implementation of test-run
U3
Transmission error between AHU and
outdoor unit
I/O transmission error
U4
I/O transmission error
Transmission error of other system
AHU system abnormal in other system
or other AHU system abnormal in own
system
U9
Erroneous field setting
System transmission malfunction
UA
Overconnection malfunction of AHUs
Malfunction of field setting
Refrigerant abnormal
Connection error (BP unit)
Faulty system malfunction
Wiring error (Auto-address error)
UH
Conflict in wiring and piping, no setting
for system
Conflict in wiring and piping
UF
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...