Troubleshooting by Indication on the Remote Controller
ESIE09-05
200
Troubleshooting
3.31
“
L1
”
Outdoor Unit: Malfunction of PC Board
Remote
Controller
Display
L1
Applicable
Models
ERQ 125 ~ 200 A7V1
Method of
Malfunction
Detection
Detect malfunctions by current value during waveform output before compressor startup.
Detect malfunctions by current sensor value during synchronized operation at the time of
startup.
Malfunction
Decision
Conditions
In case of overcurrent (OCP) during waveform output
When the current sensor malfunctions during synchronized operation
In case of IGBT malfunction
Supposed
Causes
Faulty outdoor PC board (A1P)
•
IPM failure
•
Current sensor failure
•
Failure of IGBT or drive circuit
Troubleshooting
YES
NO
Turn OFF the power
supply once and then turn
it ON again.
Does
it return normally?
It is believed that
external factors (noise,
etc.) other than failure
caused the malfunction.
Replace the outdoor PC
board (A1P).
PC board equipped with
a resin case
( )
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...