Installation and operation manual
82
EKEQMCBV3
Option kit for combination of Daikin condensing units
with field supplied air handling units
4PW52447-1
T
ROUBLESHOOTING
To set up the system and make trouble shooting possible, it is
required to connect the remote controller to the option kit.
Not a malfunction of the air conditioner
The system does not operate
■
The system does not restart immediately after the
cooling/heating is requested.
If the operation lamp lights, the system is in normal operating
condition.
It does not restart immediately because one of its safety devices
actuates to prevent the system from being overloaded. The
system will turn on again automatically after 3 minutes.
■
The system does not restart immediately after the power supply
is turned on.
Wait 1 minute until the micro computer is prepared for operation.
Trouble shooting
If one of the following malfunctions occurs, take the measures shown
below and contact your dealer.
The system must be repaired by a qualified service person.
■
If a safety device such as a fuse, a breaker, or an earth leakage
breaker frequently actuates, or ON/OFF switch does not
properly work.
Turn off the main power switch.
■
If the display
, the unit number and the operation lamp
flash and the malfunction code appears;
Notify your dealer and report the malfunction code.
If the system does not operate properly, and none of the above
mentioned malfunctions is evident, investigate the system according
to the following procedures.
If the system does not operate at all
■
Check if there is a power failure.
Wait until power is restored. If power failure occurs during
operation, the system automatically restarts immediately after
the power supply recovers.
■
Check if the fuse has blown or breaker has been tripped.
Change the fuse or set the breaker.
If the system stops operating after operation is complete
■
Check if the air inlet or outlet of outdoor or air handling unit is
blocked by obstacles.
Remove the obstacle and make it well-ventilated.
■
Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.
■
The error signal is given and the system stops.
If the error resets after 5-10 minutes, the unit safety device was
activated but the unit restarted after evaluation time.
If the error persists, contact your dealer.
If the system operates but it does not sufficiently cool/heat
■
Check if the air inlet or outlet of the air handling unit or the
outdoor unit is blocked with obstacles.
Remove the obstacle and make it well-ventilated.
■
Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.
■
Check if the doors or the windows are open.
Shut doors or windows to prevent wind from coming in.
■
Check if direct sunlight enters the room.
Use curtains or blinds.
■
Check if there are too many inhabitants in the room.
Cooling effect decreases if heat gain of the room is too large.
■
Check if the heat source of the room is excessive.
Cooling effect decreases if heat gain of the room is too large.
The air handling unit is freezing up
■
The liquid thermistor (R2T) is not put on the coldest position and
part of the air handling unit is freezing up.
Thermistor must be put on the coldest position.
■
The thermistor has come loose.
The thermistor must be fixed.
■
The air handling unit fan is not operating continuously.
When the outdoor unit stops operating, the air handling unit fan
must continue operation to melt the ice that was accumulated
during outdoor unit operation.
Ensure that the air handling unit fan keeps operating.
In these cases, contact your dealer.
M
AINTENANCE
D
ISPOSAL
REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
■
Only a qualified service person is allowed to perform
maintenance.
■
Before obtaining access to terminal devices, all power
supply circuits must be interrupted.
■
Water or detergent may deteriorate the insulation of
electronic components and result in burn-out of these
components.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...