ESIE09-05
Field Setting
Test Operation
105
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
1
Cool / Heat
Unified address
w
x
x
x
x
x
w
Address
0
wxxxxxx
∗
Binary number
1
wxxxxxw
(6 digits)
~
31
wxwwwww
2
Low noise/demand
address
w
x
x
x
x
w
x
Address
0
wxxxxxx
∗
Binary number
1
wxxxxxw
(6 digits)
~
31
wxwwwww
3
Test operation
w
x
x
x
x
w
w
Test operation : OFF
wxxxxxw
Test operation : ON
wxxxxwx
∗
5
Indoor forced fan H
w
x
x
x
w
x
w
Normal operation
wxxxxxw
∗
Indoor forced fan H
wxxxxwx
6
Indoor forced
operation
w
x
x
x
w
w
x
Normal operation
wxxxxxw
∗
Indoor forced operation
wxxxxwx
10 Defrost changeover
setting
w
x
x
w
x
w
x
Quick defrost
wxxxwxx
Normal (factory setting)
wxxxxwx
∗
Slow defrost
wxxxxxw
12 External low noise/
demand setting
w
x
x
w
w
x
x
External low noise/demand:
NO
wxxxxxw
∗
External low noise/demand:
YES
wxxxxwx
13 Airnet address
w
x
x
w
w
x
w
Address
0
wxxxxxx
∗
Binary number
1
wxxxxxw
(6 digits)
63
wwwwwww
20
Additional refrigerant
charging operation
setting
w
x
w
x
w
x
x
Refrigerant charging: OFF
wxxxxxw
∗
Refrigerant charging: ON
wxxxxwx
21
Refrigerant recovery /
vacuuming mode
setting
w
x
w
x
w
x
w
Refrigerant recovery /
vacuuming: OFF
wxxxxxw
∗
Refrigerant recovery /
vacuuming: ON
wxxxxwx
22 Night-time low noise
setting
w
x
w
x
w
w
x
OFF
wxxxxxx
∗
Level 1 (outdoor fan with 6 step or lower)
wxxxxxw
Level 2 (outdoor fan with 5 step or lower)
wxxxxwx
Level 3 (outdoor fan with 4 step or lower)
wxxxxww
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...