Field Setting
ESIE09-05
100
Test Operation
3.2 Field Setting from Outdoor Unit
3.2.1 Setting by Dip Switches
The following field settings are made by dip switches on PC board.
D-box: cool/heat selection by remote controller
F-box: no remote controller
-> cool/heat selection through ABC-contact
•
Set the remote controller only when changing over the operation mode between cooling and
heating using the remote controller installed in the outdoor.
c
Connect the cool/heat selector (optional accessory) to the terminals (A, B and C) on the
outdoor X2M Terminal board (A, B and C).
d
Set the cool/heat selector switch DS1-1 from “OFF” (which is selected at the factory before
shipment) to “ON”.
Dipswitch
Setting item
Description
No.
Setting
DS1-1
ON
Cool / Heat
change over
setting
Used to set cool / heat change over setting by remote
controller equipped with outdoor unit. (Note 1)
OFF (Factory set)
DS1-2
ON
Not used
Do not change the factory settings.
OFF (Factory set)
Cool/heat selector connection procedure
X2M
A1P
A B C
DS1-1
switch knob
A B C
Cool/heat
selector (option KRC 19-26 A6)
ON/OFF
DS1 1 2
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...