ESIE09-05
Symptom-based Troubleshooting
Troubleshooting
153
15 LCD display "88"
appears on the
remote
controller.
Immediately after turning ON
the power supply
The reason is that the system is
checking to be sure the remote
controller is normal.
Normal operation.
This code is displayed for a period
of approximately one minute at
maximum.
16 The outdoor unit
compressor or
the outdoor unit
fan does not
stop.
After stopping operation
It stops in order to prevent oil or
refrigerant from dwelling.
Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.
17 The outdoor gets
hot.
While stopping operation
The reason is that the compressor
is warmed up to provide smooth
startup of the system.
Normal operation.
18 Hot air comes
out from the
system even
though it stops.
Hot air is felt while the system
stops.
On VRV systems, small quantity
of refrigerant is fed to AHUs in the
stopped state when other AHUs
are in operation.
Normal operation.
19 The system does
not cool air well.
The system is in dry operation. The reason is that the dry
operation serves not to reduce
the room temperature where
possible.
Change the system to cooling
operation.
Symptom
Supposed Cause
Countermeasure
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...