ESIE09-05
Combination Table
General Information
5
2. Combination Table
Heat pump
P: Pair: Combination depending on AHU heat exchanger volume and capacity.
Saturated suction temperature (SST) = 6°C, SH (superheat) = 5 K, air temperature = 27°C DB /
19°C WB.
Note:
If conflicting result occurs, capacity selection has priority over volume.
Control box
Expansion valve kit
Outdoor unit
EKEQDCBV3 EKEQFCBV3
EKEXV63
EKEXV80
EKEXV100
EKEXV125
EKEXV140
single
phase
ERQ100
P
P
P
P
P
P
-
ERQ125
P
P
P
P
P
P
P
ERQ140
P
P
-
P
P
P
P
Allowed heat exchanger volume (dm
3
) Allowed heat exchanger capacity (kW)
EKEXV class
Minimum
Maximum
Minimum
Maximum
63
1.66
2.08
6.3
7.8
80
2.09
2.64
7.9
9.9
100
2.65
3.3
10
12.3
125
3.31
4.12
12.4
15.4
140
4.13
4.62
15.5
17.6
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...