Troubleshooting by Indication on the Unified ON/OFF Controller
ESIE09-05
224
Troubleshooting
[CHECK 1] Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Short circuit
Rise in high
pressure
Local
pressure
rise
High pipe
resistance
Stop valve closed
Bent or crashed pipe
Clogging of foreign
particles
Check to be sure the stop valve is open.
Conduct visual checks for pipe conditions.
Is there any temperature difference caused before
and after the filter or branch pipe.
[In cooling]
If the outdoor unit electronic
expansion valve is throttled:
(See *1.)
Faulty outdoor
unit electronic
expansion valve
Faulty indoor
unit electronic
expansion valve
Faulty valve coil
Faulty valve body
Are the coil resistance and insulation normal?
A temperature difference in excess of 10°C
between the inlet and the outlet is deemed to be abnormal.
Faulty
control
Faulty high pressure sensor
Faulty control PCB
Are the electrical characteristics normal?
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
Are the coil resistance and insulation
normal?
Faulty high
pressure
control
Faulty valve coil
Faulty valve body
[In heating]
If the AHU electronic expansion
valve excessively throttled:
(See *2.)
Faulty
control
Faulty high pressure sensor
Faulty AHU
liquid pipe thermistor
Faulty control PCB
Are the electrical characteristics normal?
In the connector properly connected?
Are the thermistor resistance characteristics normal?
Is the pressure value checked with the Service
Checker corresponding to the measurement of the
pressure sensor?
[In cooling]
High suction
air
temperature
of the
condenser
[In heating]
High suction air
temperature
of outdoor unit
Short circuit
High ambient temperature
Is the suction air temperature not more than 46°C?
Is the outdoor temperature not more than 46°C?
High suction
air temperature
of AHU
High ambient temperature
Is the suction air temperature not more than 27°C?
Is the indoor temperature not more than 27°C?
Faulty suction air thermistor of AHU
High suction air temperature of outdoor unit
Faulty outdoor temperature thermistor of outdoor unit
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Is the outdoor temperature not more than 16°CWB?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation
in condensing
capacity
Dirty condenser
Mixing of non-condensable gas
Is the heat exchanger clogged? (In cooling)
Is air or else mixed in the refrigerant system?
Decreased
fan airflow
rate
Decreased
fan
output
Faulty fan
motor
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
If a spare PC board is mounted, is the
capacity setting properly made?
Faulty control
PC board
(Including
capacity setting)
High air
passage
resistance
Dirty filter
Is the air filter clogged?
Obstacle
Is there any obstacle in the air passage?
Excessive refrigerant charging
Improper model selection [In heating]
Refer to “F6” Outdoor unit: Refrigerant Overcharged.
Is the AHU too small compared to the
large-sized outdoor unit?
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
*2: In heating, the AHU electronic expansion valve is used for “subcooled degree control”.
C: SDK04009
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...