Field Setting
ESIE09-05
106
Test Operation
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
25 Low noise setting
w
x
w
w
x
x
w
Level 1 (outdoor fan with 6 step or lower)
wxxxxxw
Level 2 (outdoor fan with 5 step or lower)
wxxxxwx
∗
Level 3 (outdoor fan with 4 step or lower)
wxxxwxx
26
Night-time low noise
operation start
setting
w
x
w
w
x
w
x
About 20:00
wxxxxxw
About 22:00 (factory setting)
wxxxxwx
∗
About 24:00
wxxxwxx
27 Night-time low noise
operation end setting
w
x
w
w
x
w
w
About 6:00
wxxxxxw
About 7:00
wxxxxwx
About 8:00 (factory setting)
wxxxwxx
∗
28 Power transistor
check mode
w
x
w
w
w
x
x
OFF
wxxxxxw
∗
ON
wxxxxwx
29 Capacity
precedence setting
w
x
w
w
w
x
w
OFF
wxxxxxw
∗
ON
wxxxxwx
30 Demand setting 1
w
x
w
w
w
w
x
60 % demand
wxxxxxw
70 % demand
wxxxxwx
∗
80 % demand
wxxxwxx
32 Normal demand
setting
w
w
x
x
x
x
x
OFF
wxxxxxw
∗
ON
wxxxxwx
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...