Troubleshooting by Indication on the Remote Controller
ESIE09-05
168
Troubleshooting
3.4 Abnormal Power Supply Voltage
Remote
Controller
Display
A8
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detection
Detect malfunction checking the input voltage of fan motor.
Malfunction
Decision
Conditions
When the input voltage of fan motor is 150V and below, or 386V and above.
Supposed
Causes
The possible causes are:
Power-supply voltage malfunction.
Connection defect on signal line.
Wiring defect.
Instantaneous blackout, others.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check the condition of the
power source.
���
Check if power-supply voltage
is 220V - 240V ± 10%.
���
Check if there is power open
phase or faulty wiring.
���
Check if power-supply voltage
side unbalance is within 6V.
"
)&
"
Reoccurrence of
malfunction.
YES
Check and correct each
wiring.
It is possible to have external
factor, such as brownout and
instantaneous blackout.
There
are problems on the
condition of power source
described
above.
YES
Correct any fault.
NO
NO
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...