Troubleshooting by Indication on the Unified ON/OFF Controller
ESIE09-05
226
Troubleshooting
[CHECK 3] Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector on motor side disconnected, measure the resistance between
each pin, then make sure that the resistance is more than the value mentioned in the
following table.
Measurement point
Judgment
1 - 4
1M
Ω
or more
2 - 4
100k
Ω
or more
3 - 4
100
Ω
or more
4 - 7
100k
Ω
or more
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
GND