ESIE09-05
Field Setting
Test Operation
95
(2) Control Setting for EKEQF-Box
With the EKEQF-box, 2 types of control are possible:
x-control: with DDC-controller
y-control: no DDC-controller.
For more information about x-, y-control, refer to “Part 6 Control Box EKEQ - CBV3”.
(3) Indoor Fan Control
In cooling and fan only mode, the indoor fan is in ON-mode when the unit is working.
In heating, different situations are possible.
Fan off during thermo off and fan on during defrost/oil return will result in fan on during thermo
off.
(4) Hot Start
During hot start, fan on is carried out when T
c
is A°C or after B minutes.
Mode n°
Setting switch n° Setting position n°
Setting
23 (13)
0
01
x-control
02
y-control
Mode n°
Setting switch n° Setting position n°
Setting
22 (12)
3
01
Fan ON at thermo off
02
Fan ON at thermo off
03
Fan OFF at thermo off
23 (13)
8
01
Fan OFF at defrost and oil return
02
Fan ON at defrost and oil return
03
Fan ON at defrost and oil return
Mode n°
Setting switch n° Setting position n°
Setting
23 (13)
7
01
A = 34°C
02
A = 37°C
03
A = 40°C
04
A = 43°C
6
01
B = 0 min
02
B = 1 min
03
B = 3 min
04
B = 5 min
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...