Troubleshooting by Indication on the Remote Controller
ESIE09-05
176
Troubleshooting
3.10
“
C6
”
AHU: Failure of Combination (Between AHU PC
Board and Fan PC Board)
Remote
Controller
Display
C6
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detection
Conduct open line detection with PC board for fan (A2P) using indoor PC board (A1P).
Malfunction
Decision
Conditions
When the communication data of PC board for fan (A2P) is determined as incorrect.
Supposed
Causes
The possible causes are:
Malfunction of PC board for fan (A2P).
Connection defect of capacity setting adapter.
Setting mistake on site.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Replace it with correct PC board
for fan (A2P).
NO
NO
Install correct capacity setting
adaptor.
After establishing transmission for
indoor and outdoor, diagnose the
operation again.
YES
YES
Is the type
of PC board for fan (A2P)
correct?
Was
correct capacity
setting adaptor installed
when replacing
it with supplementary
PC board?
Was indoor
PC board (A1P) replaced
with supplementary
PC board?
YES
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...