ESIE09-05
Troubleshooting by Indication on the Remote Controller
Troubleshooting
169
3.5
“
A9
”
AHU: Malfunction of Moving Part of Electronic
Expansion Valve (Y1E)
Remote
Controller
Display
A9
Applicable
Models
All AHU models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Malfunction of moving part of electronic expansion valve
Defect of AHU PC board
Defect of connecting cable
Troubleshooting
(V2781)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
After connecting, turn the power
supply off and then back on.
Replace the moving part of the
electronic expansion valve.
YES
YES
NO
NO
Replace the connecting cable.
If you turn the power supply off
and turn on again, and it still does
not help, replace the AHU PC
board.
NO
YES
The
electronic
expansion valve is
connected to X7A of the
AHU PC
board.
Normal
when coil check
(
∗
1) of the moving part of
the electronic expansion
valve is
checked.
The connecting
cable is short-circuited or
disconnected.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...