Troubleshooting by Indication on the Remote Controller
ESIE09-05
196
Troubleshooting
3.27
“
J7
”
Outdoor Unit: Malfunction of Thermistor (R7T) for
Outdoor Unit Liquid Pipe
Remote
Controller
Display
J7
Applicable
Models
ERQ 125 ~ 200 A7V1
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the liquid pipe thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Defect of thermistor (R7T) for outdoor unit liquid pipe
Defect of outdoor unit PC board (A1P)
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P232.
(V3074)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R4T) from the outdoor
unit PC board.
(3.5k
Ω
~
360k
Ω
)
Replace outdoor unit PC board
(A1P).
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R6T).
YES
YES
Connector
is connected to X13A of
outdoor unit PC board
(A1P).
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...