I nst alling ant ennas and I RFUs
Chapt er 5: I nst allat ion
5- 76
phn- 2513_004v000 ( Oct 2012)
Connecting power to the IRFU
Connect the power supply cable to the IRFU (
). Check that the power connector
screws are tight enough to hold the power cable securely in place.
For EMI Class B compliance, a 10 AWG braided shielded power cable with drain wire and
foil is recommended.
If a battery is being used to supply power, connect the ‘common’ battery terminal to the
main electrical grounding system (not directly to the building grounding system).
Figu r e 9 3
I RFU pow er connect ion