120
SAW sensor - Parameter
Type 8098
13.10.4
Disabling the diagnostics for special events on the electronics
Only for variant with outputs.
By default, all the diagnostics related to the electronics are disabled.
To disable the diagnostics for special events on the electronics, do the following:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Diag events
→
Electronic
→
Select the special event
→
Select
None
The diagnostics of the special event are disabled.
13.10.5
Enabling the diagnostics for special events on the sensor
By default, all the diagnostics related to the sensor are disabled.
To enable the diagnostics for special events related to the sensor, do the following:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Diag events
→
Sensor
→
Select the special event
→
Assign a device status to the special event:
Failure
,
Out of specification
,
Maintenance required
or
Normal state
.
The diagnostics of the special event are enabled.
→
To be informed that an event occurs, activate all the diagnostics on the device. See chpt.
English