118
SAW sensor - Parameter
Type 8098
Is the event associated to the device
status
Out of specification
?
Yes
The status indicator is yellow.
The analogue outputs react depending
on the behaviour selected for
Out of
specification
events.*)
If a digital output is configured as
an on/off output to switch on
Out of
specification
events, the on/off output
switches depending on the event.*)
Is the event associated to the device
status
Maintenance required
?
Yes
The status indicator is blue.
The analogue outputs react depending
on the behaviour selected for
Mainte
-
nance required
events.*)
If a digital output is configured as an on/
off output to switch on
Maintenance
required
events, the on/off output
switches depending on the event.*)
... continued from the previous page.
No
Figure 26:
Flowchart: operating of the diagnostics when a special event occurs (part 2/2)
*
)
Only variant with outputs.
13.10.1
Enabling the diagnostics for special events in the process
By default, all the diagnostics related to the process are disabled.
To enable the diagnostics for special events related to the process, do the following:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Diag events
→
Process
→
Select the special event
→
Assign a device status to the special event:
Failure
,
Out of specification
,
Maintenance required
or
Normal state
.
The diagnostics of the special event are enabled.
→
To be informed that an event occurs, activate all the diagnostics on the device. See chpt.