98
SAW sensor - Parameter
Type 8098
13.7.6
Resetting the default values of the error limits, the warning
limits and the hysteresis of each totalizer
The default values of the error limits, the warning limits and the hysteresis of the totalizers are the following:
• high error value: 10,000,000 m
3
• low error value: –10,000,000 m
3
• high warning value: 8,000,000 m
3
• low warning value: –8,000,000 m
3
• value of the hysteresis: 0.0 m
3
To reset the default values of the error limits, the warning limits and the hysteresis of each totalizer, do the following:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Stand. meas. values
→
Totalizer 1
or
Totalizer 2
→
Limits
→
Reset to default
→
Finish
The limit values and the hysteresis value are reset.
13.7.7
Enabling the user to start, stop or reset each totalizer
By default, the user is not allowed to start, to stop or to reset a totalizer.
To authorize the user to start, to stop or to reset a totalizer, do the following:
→
Select the device in the navigation area.
→
SAW sensor
→
Parameter
→
Stand. meas. values
→
Totalizer 1
or
Totalizer 2
→
Start/Stop/Reset
→
Select
Enabled
The user is authorized to start, to stop or to reset a totalizer.
English