![Burkert FLOWave S 8098 Скачать руководство пользователя страница 166](http://html1.mh-extra.com/html/burkert-0/flowave-s-8098/flowave-s-8098_operating-instructions-manual_2832470166.webp)
166
Outputs - Maintenance
Type 8098
18.6
Checking the correct operation of a frequency output
To check the correct operation of a digital output configured as a frequency output, do the following:
→
Connect a frequency meter to the digital output configured as a frequency output.
→
Energize the output.
→
Select the device in the navigation area.
→
Outputs
→
Maintenance
→
Output 2: digital
or
Output 3: digital
, configured as a frequency output
→
Test
→
Enter a frequency value
→
Check if the output is operating correctly.
→
Finish
18.7
Checking the correct operation of a pulse output
To check the correct operation of a digital output configured as a pulse output, do the following:
→
Connect a counter to the digital output configured as a pulse output.
→
Energize the output.
→
Select the device in the navigation area.
→
Outputs
→
Maintenance
→
Output 2: digital
or
Output 3: digital
, configured as a pulse output
→
Test
→
Enter a frequency value
→
Enter a number of pulses
→
Check if the output is operating correctly.
→
Finish
English