11.3 Control the Motor
WARNING
Ensure the enclosure is in place before the device is powered on. Wait for at
least 5 minutes after powering off to allow the DC capacitor being discharged,
and do not remove the cover during this period!
Step
Operation
Description
1
Rotate the potentiometer counterclockwise
(leftwards) to the greatest extent
Output frequency setting is 0.00
2
Press <Run> button
Control command active, 0.00 is displayed
3
Rotate the potentiometer clockwise (right-
wards) slowly till 5.00 is displayed
The motor starts to run
Observe the running status:
If the motor runs in the correct direction
If the motor runs steadily
If there is any abnormal noise or problem
Recommended operation:
Stop the motor immediately by switching off
the power if any abnormality occurs
Restart commissioning only after error cau-
ses have been removed
4
Rotate the potentiometer clockwise
The motor accelerates
5
Rotate the potentiometer counterclockwise The motor decelerates
6
Press <Stop> button
Stop command activated, the motor stops
7
Check parameters without load
Settings according to actual applications
8
Check parameters with load
Settings according to actual applications
Tab. 11-5: Motor controlling procedure
●
After powering on, VFC 3210 will generate output if pressing down the <Run>
button (or 'Control by terminals' is activated).
●
By default, VFC 3210 is set as:
– The frequency converter is started or stopped by the operating panel.
– The output frequency is set by the potentiometer on the operating panel.
●
After powering on, please confirm:
– The setting frequency is displayed (no error display).
– The monitoring parameter is consistent with the actual situations.
●
By default, Output frequency in run status and Setting frequency in stop sta-
tus are displayed as the monitoring parameters, which can be changed to oth-
er parameters with parameters U1.00 and U1.10. The default settings are
based on standard applications with standard motors.
VFC 3210
Bosch Rexroth AG
Quick Start
DOK-RCON04-VFC3210****-IT01-EN-P
71/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...