Fig. 12-59: Automatic torque boot with square V/f curve
For further adjustment of the voltage boost, set parameter C2.22 'Automatic tor-
que boost factor'. Its default value 50 % means no adjustment. The calculation
equation is shown as below:
[Voltage boost] = √3 x 0.5 x I
1
x R
1
x [C2.22]
R
1
: stator resistance
I
1
: stator current
Thus R
1
should be preset or calculated or tuned, and then input to [C1.21].
Bosch Rexroth AG
Functions and Parameters
VFC 3210
172/253
DOK-RCON04-VFC3210****-IT01-EN-P