8.2 Cable Specifications
8.2.1 Power Cables
Cable specification for international without USA / Canada
●
ONLY USE copper wires of 90 ℃ or above with XLPE or EPR insu-
lation according to IEC60364-5-52.
●
It is recommended to use shielded cables to connect the motor.
VFC 3210
Model
Fuse (gG)
Power cables installation mode
PE Cable
Torque / Screw
B1
B2
E
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[mm
2
]
[N·m / lbf·in] (Mx)
0K40
10.0
2.5
2.5
2.5
10.0
0.8 / 7 (M3)
0K75
16.0
2.5
2.5
2.5
10.0
0.8 / 7 (M3)
1K50
25.0
4.0
4.0
2.5
10.0
0.8 / 7 (M3)
2K20
32.0
6.0
6.0
4.0
10.0
0.8 / 7 (M3)
Tab. 8-1: 1P 200 VAC fuse and cable dimensions for international without USA / Canada
VFC 3210
Model
Fuse (gG)
Power cables installation mode
PE Cable
Torque / Screw
B1
B2
E
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[mm
2
]
[N·m / lbf·in] (Mx)
0K40
6.0
2.5
2.5
2.5
10.0
0.8 / 7 (M3)
0K75
10.0
2.5
2.5
2.5
10.0
0.8 / 7 (M3)
1K50
10.0
2.5
2.5
2.5
10.0
0.8 / 7 (M3)
2K20
16.0
2.5
2.5
2.5
10.0
0.8 / 7 (M3)
4K00
20.0
4.0
4.0
2.5
10.0
0.8 / 7 (M3)
Tab. 8-2: 3P 400 VAC fuse and cable dimensions for international without USA / Canada
Bosch Rexroth AG
Frequency Converter Wiring
VFC 3210
32/253
DOK-RCON04-VFC3210****-IT01-EN-P
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...