6.1.7 Protection
Over current protection, over- / under- voltage protection, surge current / short circuit protection, in-
put / output phase loss protection, converter over- / under- temperature protection, motor overload
protection, motor over temperature protection, direction lock protection, analog input broken wire de-
tection, etc.
6.1.8 Conditions
Rated ambient temperature
-10...40 ℃
Derating / ambient temperature
1.5 % / 1 °C (40...50 °C)
Rated storage temperature
-20...60 ℃
Rated altitude
≤ 1,000 m
Derating / altitude
1 % / 100 m (1,000...2,000 m)
Relative humidity
≤ 90 % RH (No condensation)
Degrees of protection
IP 20 (Mounting on the metal wall in control cabinet )
Degrees of pollution
2 (EN 50178)
Vibration
10 Hz ≤ f ≤ 57 Hz amplitude: 0.075 mm
57 Hz < f ≤ 150 Hz acceleration: 1 g
Mounting mode
Wall mounting
Cooling type
Natural cooling (≤ 0K75)
Enforced air cooling (≥ 1K50)
Certification
CE
VFC 3210
Bosch Rexroth AG
Frequency Converter Overview
DOK-RCON04-VFC3210****-IT01-EN-P
21/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...