Additional status register (0x7FA1)
Additional status register is the extension of main status register(7FA0H), it
stores other status information of frequency converter. This register is read-only.
The definition of each bit is shown in the table below:
bit
Value
Description
15
1
Error
0
No error
14
-
Reserved
13
-
Reserved
12
-
Reserved
11
1
Coasting to stop
0
Not coasting
10
1
Speed tracing
0
Not tracing
9
1
0 speed
0
Not 0 speed
8
1
DC braking
0
Not DC braking
7
-
Reserved
6
1
Stall over current
0
Normal
5
1
Stall over voltage
0
Normal
4
1
Decelerating
0
Not in deceleration
3
1
Accelerating
0
Not in acceleration
2
1
Jogging
0
Not in jog
1
1
Running
0
Stop
0
1
Reverse
0
Forward
Tab. 14-26: Additional status register (0x7FA1)
VFC 3210
Bosch Rexroth AG
Communication
DOK-RCON04-VFC3210****-IT01-EN-P
203/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...