Communication state register (0x7FA0)
The frequency converter state can be monitored by reading the register. This
register is read-only. The definition of each bit is shown in the table below:
bit
Value
Description
15 ... 8
–
Error code (equals to [E9.05])
7
1
Error
0
No error
6
1
Stall over current
0
Normal
5
1
Stall over voltage
0
Normal
4
1
Decelerating
0
Not in deceleration
3
1
Accelerating
0
Not in acceleration
2
1
Jogging
0
Not in jog
1
1
Running
0
Stop
0
1
Reverse
0
Forward
Tab. 14-25: Communication state register (0x7FA0)
Bosch Rexroth AG
Communication
VFC 3210
202/253
DOK-RCON04-VFC3210****-IT01-EN-P