3: First frequency setting * Second frequency setting
The actual setting frequency is the result of the multiplication operation of
the first and second frequency setting sources.
●
4: Bigger one of 2 sources
The actual setting frequency is the bigger one of the first and second frequen-
cy setting sources.
●
5: Smaller one of 2 sources
The actual setting frequency is the smaller one of the first and second fre-
quency setting sources.
●
6: Valid which channel is non-zero
If the first frequency setting sources ≠ 0Hz and the second frequency setting
sources ≠ 0Hz; then the actual setting frequency is the first frequency setting
sources.
If the first frequency setting sources ≠ 0Hz and the second frequency setting
sources = 0Hz; then the actual setting frequency is the first frequency setting
sources.
If the first frequency setting sources = 0Hz and the second frequency setting
sources ≠ 0Hz; then the actual setting frequency is the second frequency set-
ting sources.
If the first frequency setting sources = 0Hz and the second frequency setting
sources = 0Hz; then the actual setting frequency is 0 Hz.
To use the frequency setting source combination function, take the following
steps:
Step 1: Be sure that [E1.00] ≠ '30: Second frequency setting source activation'
to deactivate the frequency setting source switching function
Step 2: Set parameter E0.00 and E0.02 to select the first and second frequency
setting sources
Step 3: Set parameter [E0.04] = 1 or 2 according to the actual application
The result of the combination is always limited within the range of
0.00…[E0.09] Hz.
Adjust the setting frequency by panel potentiometer
By default, the first frequency setting source is from the potentiometer on the
operating panel. To adjust the output frequency, follow the instructions below:
●
Rotate the potentiometer counterclockwise (leftwards)
The output frequency decreases, and the motor decelerates.
●
Rotate the potentiometer clockwise (rightwards)
The output frequency increases, and the motor accelerates.
VFC 3210
Bosch Rexroth AG
Functions and Parameters
DOK-RCON04-VFC3210****-IT01-EN-P
93/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...