Connect switch K2 to X2, and set [E1.01] = '21: Frequency Down command'.
K1
K2
K3
Response of setting frequency
Closed / Open
Closed / Open
Closed
Is reset to 0.00 Hz
Closed
Open
Open
Increases from [E1.17] with the
change rate defined by [E1.16]
Open
Closed
Open
Decreases from [E1.17] with the
change rate defined by [E1.16]
Open
Open
Open
No change
Closed
Closed
Open
No change
Tab. 12-1: K1, K2, K3 settings
Up / Down / Reset command is only active when the frequency con-
verter is running. Whether the setting frequency modified by Up /
Down terminals will be saved or not after power off depends on
chapter 12.4.5 "Frequency Setting Saving" on page 106
.
Bosch Rexroth AG
Functions and Parameters
VFC 3210
96/253
DOK-RCON04-VFC3210****-IT01-EN-P