
Troubleshooting
SuperTrak™ GEN3 System Operation and Maintenance Manual
265
Rev. 9 (12-2021)
Test the Status of the Hardware
1. Open TrakMaster.
2. In the left pane, click
Diagnostic
>
Hardware Status
.
3. Verify that the
State
of all motor temperature sensors is set to
Monitored
.
4. Verify that the
Value
for:
• Motor temperature
sensors are reasonable.
This value varies
depending on the state
of the system.
NOTE: All sections have two (2) coil driver boards with the exception of the
180 deg. (800 mm) section which has three (3). Each coil driver board has
five (5) thermistor connections; straight sections and 90 deg. sections have
ten (10) thermistors while 180 deg. (800mm) sections have fifteen (15).
A 180 deg. (500mm) section has only six (6) thermistor locations, and thus
only uses three (3) connections per coil driver board. As a result
thermistors 2 and 4 (Left and Right) are set to “Ignored” by default in
TrakMaster.
• Electronics temperatures are within a reasonable range (25-50°C [77-
122°F]).
• Motor voltages are representative of the current SuperTrak power supply
power state (ON or OFF), and are within a reasonable range (27-29V).
Содержание SuperTrak GEN3
Страница 1: ...Rev 9 December 2021...
Страница 2: ......
Страница 3: ...SuperTrak GEN3 Conveyance Platform Modular Conveyor Operation and Maintenance Manual...
Страница 6: ......
Страница 12: ...This page is intentionally blank...
Страница 30: ...This page is intentionally blank...
Страница 58: ...This page is intentionally blank...
Страница 296: ...This page is intentionally blank...
Страница 300: ...This page is intentionally blank...
Страница 364: ...This page is intentionally blank...
Страница 366: ...This page is intentionally blank...