Troubleshooting
SuperTrak™ GEN3 System Operation and Maintenance Manual
257
Rev. 9 (12-2021)
5. Measure the
resistance between
the motor body and
the 1st pin on the
terminal block plug.
The resistance should
show higher than 0.6
Ω
.
If the resistance is 0.6 or
lower, the coil is shorted.
The coils are not
serviceable , so the
motor may need to be
returned for repair.
6. Measure the
resistance between
the motor body and
the 3rd pin on the
terminal block plug.
Same as prior step: the
resistance should show
higher than 0.6
Ω
. If
the resistance is 0.6 or
lower, the coil is shorted.
The coils are not
serviceable , so the
motor may need to be
returned for repair.
7. Repeat the steps above for all terminal block plugs in the section’s coil driver board.