SuperTrak™ GEN3 System Operation and Maintenance Manual
Rev. 9 (12-2021)
Troubleshooting
Test the Coil Functionality
1. Remove all pallets from the straight section or 180 deg. section to be tested.
2. Turn the SuperTrak power supply power ON.
This is generally done by turning the system power ON when the safety circuit
is closed.
3. Open TrakMaster.
4. In the left pane, click
Advanced
>
Coil Control
.
5. Click
Check All
.
6. Verify that the section is disabled and that there are no active faults or
warnings.
The top right of the screen displays
Disabled
when faults or warnings exist. If
required, open the Section Status/Control screen to clear any faults or
warnings.
7. Verify that the
Setpoint
is set to 5.00 A.
Содержание SuperTrak GEN3