Name
Range
Step
Default
Networks placement atm
-360.000...360.000deg
0.001deg
0deg
Synchronizing time left
0.000...1800.000s
0.005s
0s
Get measurement errors for fine tuning
0: -
1: Get errors
-
0: -
Magnitude difference fine tune
-200.000...200.000%
0.001%
0%
Frequency difference fine tune
-100.000...100.000Hz
0.001Hz
0Hz
Angle difference fine tune
-360.000...360.000deg
0.001deg
0deg
Table. 5.5.9 - 283. Synchronizing settings.
Name
Range
Step
Default
Maximum allowed voltage difference
0.10...50.00%Un
0.01%Un
2.00%Un
Maximum allowed overfrequency difference to allow
synchronizing
0.00...2.00Hz
0.01Hz
0.2Hz
Maximum allowed underfrequency difference to allow
synchronizing
0.00...2.00Hz
0.01Hz
0Hz
Maximum time for synchronizing
0.000...1800.000s
0.005s
300.000s
Maximum allowed angular disposition to allow synchronizing
-25.00...25.00deg
0.01deg
10.00deg
Adjustment for measurement inaccuracy or set of desired volt.
offset
-95.0000...95.0000%Un 0.0001%Un 0%Un
Adjustment for measurement inaccuracy or set of desired angular
offset
-60.0000...60.0000deg
0.0001deg
0deg
Adjustment for measurement inaccuracy or set of desired freq.
offset
-0.5000...2.0000Hz
0.0001Hz
-0.1000Hz
Voltage adjustment slope
0.00...25.00%/s
0.01%/s
0.20%/s
Volt. Max. adjustment pulse length
0.000...1800.000s
0.005s
3.000s
Volt. Min. adjustment pulse length
0.000...1800.000s
0.005s
0.100s
Volt. Min. Resting time between pulses
0.000...1800.000s
0.005s
2.500s
Freq. Max. adjustment pulse length
0.000...1800.000s
0.005s
3.000s
Freq. Min. adjustment pulse length
0.000...1800.000s
0.005s
0.100s
Freq. Min. Resting time between pulses
0.000...1800.000s
0.005s
2.500s
Frequency adjustment slope when increasing
0.00...10.00Hz/s
0.01Hz/s
0.10Hz/s
Frequency adjustment slope when decreasing
-10.00...0.00Hz/s
0.01Hz/s
-0.10Hz/s
Circuit breaker pre-closing time incl auxiliary relays
0.000...1800.000s
0.005s
0.100s
Lenght of circuit breaker closing pulse
0.000...1800.000s
0.005s
0.250s
Multiple On pulses
0: Single On pulse
1: Multiple pulses
-
0: Single On
pulse
Table. 5.5.9 - 284. Synchronizer internal parameters.
Name
Range
Step
Default
Maximum allowed voltage difference to start synchronizing
0.00...50.00%Un
0.01%Un
20.00%Un
Block voltage up commands over
0.00...50.00%Un
0.01%Un
20.00%Un
Block voltage down commands under
-50.00...50.00%Un
0.01%Un
-20.00%Un
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
354
© Arcteq Relays Ltd