Calculated measurement
Three-phase power factor
Pick-up
Pick-up setting
0.00…0.99, setting step 0.01
Inaccuracy:
- power factor (when U > 1.0 V and I > 0.1 A)
±0.001
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (at least 0.01 below the setting)
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- at least 0.01 below the setting
<50 ms
Reset
Reset ratio
1.03 of the power factor setting
Reset time
<50 ms
No
Notte!
e!
• The minimum voltage for the power factor calculation is 1.0 V secondary and the minimum
current is 0.1 A secondary.
10.2.1.21 Volts-per-hertz overexcitation protection (V/Hz>; 24)
Table. 10.2.1.21 - 462. Technical data for the volts-per-hertz overexcitation protection function.
Measurement inputs
Voltage input
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
Voltage input magnitude
Maximum line-to-line voltage
Frequency reference 1
Frequency reference 2
Frequency reference 3
CT1IL1, CT2IL1, VT1U1, VT2U1
CT1IL2, CT2IL2, VT1U2, VT2U2
CT1IL3, CT2IL3, VT1U3, VT2U3
Pick-up
Pick-up setting
0.01…75.00 %, setting step 0.01 %
Inaccuracy:
- V/Hz
±1.0 %
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (VHZ
M
/VHZ
SET
ratio 1.05)
±1.0 % or ±25 ms
Instant operation time
Start time and instant operation time (trip):
- VHZ
M
/VHZ
SET
ratio 1.05)
<40 ms
Reset
Reset ratio
97 % of the pick-up setting
Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±25 ms
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
546
© Arcteq Relays Ltd
IM00001