Name
Range
Step
Default
Function
Description
LV side
nominal
voltage
0.1…500.0kV
0.1kV
110.0kV
All
The LV side nominal voltage of the transformer. This
value is used to calculate the nominal currents of the
LV side.
Transformer
Zk%
0.01…25.00%
0.01%
3.00%
Info
The transformer's short-circuit impedance in
percentages. Used for calculating short-circuit
current.
Transformer
nom. freq.
10…75Hz
1Hz
50Hz
Info
The transformer's nominal frequency. Used for
calculating the transformer's nominal short-circuit
inductance.
Transf. vect.
group
0: Manual
1: Yy0
2: Yyn0
3: YNy0
4: YNyn0
5: Yy6
6: Yyn6
7: YNy6
8: YNyn6
9: Yd1
10: YNd1
11: Yd7
12: YNd7
13: Yd11
14: YNd11
15: Yd5
16: YNd5
17: Dy1
18: Dyn1
19: Dy7
20: Dyn7
21: Dy11
22: Dyn11
23: Dy5
24: Dyn5
25: Dd0
26: Dd6
-
1: Yy0
- transformer
status
monitoring
- transformer
differential
The selection of the transformer's vector group. The
selection values (1–26) are predefined so that the
scaling and vector matching are applied in the relay
automatically when the correct vector group is
selected.
The predefinitions assume that the HV side is
connected to the CT1 module and that the LV side is
connected to the CT2 module.
If the protected transformer vector group is not found
in the predefined list, it can be manually set by
selecting the option "0: Manual set".
HV side Star
or Zigzag/
Delta
0: Star/Zigzag
1: Delta
-
0: Star/
Zigzag
- transformer
status
monitoring
- transformer
differential
The selection of the HV side connection. Can be
selected between star or zigzag and delta. This
selection is visible only if the option "Manual set" is
selected for the vector group setting.
HV side
grounded
0: Not
grounded
1: Grounded
-
0: Not
grounded
- transformer
status
monitoring
- transformer
differential
The selection of whether or not the zero sequence
compensation is applied in the HV side current
calculation. The selection is visible only if the option
"Manual set" is selected for the vector group setting.
HV side lead
or lag LV
0: Lead
1: Lag
-
0: Lead
- transformer
status
monitoring
- transformer
differential
The selection of whether the HV side leads or lags the
LV side. The selection is visible only if the option
"Manual set" is selected for the vector group setting.
LV side Star/
Zigzag or
Delta
0: Star/Zigzag
1: Delta
-
0: Star/
Zigzag
- transformer
status
monitoring
- transformer
differential
The selection of the LV side connection. Can be
selected between star or zigzag and delta. This
selection is visible only if the option "Manual set" is
selected for the vector group setting.
LV side
grounded
0: Not
grounded
1: Grounded
-
0: Not
grounded
- transformer
status
monitoring
- transformer
differential
The selection of whether or not the zero sequence
compensation is applied in the LV side current
calculation. The selection is visible only if the option
"Manual set" is selected for the vector group setting.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
285