Time remaining
to trip
-1800.000...1800.000s 0.005s When the function has detected a fault and counts down time towards a
trip, this displays how much time is left before tripping occurs.
PF
meas
/ PF
set
at the moment
0.00...1250.00
0.01
The ratio between the measured power factor and the pick-up value.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a START signal is generated and the function proceeds to the time
characteristics calculation.
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and processes the release time characteristics similarly to when the pick-up
signal is reset.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup current values and its fault type to be issued.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Operating time characteristics for trip and reset
This function supports definite time delay (DT). For detailed information on these delay types please
refer to the chapter "General properties of a protection function" and its section "Operating time
characteristics for trip and reset".
Events and registers
The power factor protection function (abbreviated "UPF" in event block names) generates events and
registers from the status changes in ALARM START, ALARM, START, TRIP and BLOCKED. The user
can select which event messages are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.16 - 155. Event messages.
Event block name
Event names
UPF1
Block ON
UPF1
Block OFF
UPF1
Start ON
UPF1
Start OFF
UPF1
Trip ON
UPF1
Trip OFF
UPF1
Alarm Start ON
UPF1
Alarm Start OFF
UPF1
Alarm ON
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
174
© Arcteq Relays Ltd