Name
Range
Step
Default
Description
PWM IGBT
temperature
0.00…500.00ºC
0.01ºC
-
Displays the temperature measurement value of the active
bridge.
PWM DC link
voltage
0.00…500.00VDC 0.01VDC -
Displays the DC link voltage measurement value of the active
bridge.
PWM DC link
current
0.000…500.000A
0.001A
-
Displays the DC link current measurement value of the active
bridge. This current is the excitation current.
Table. 6.2.2.5 - 378. Active bridge DO status and control.
Name
Range
Step Default
Description
Active
bridge
DOx
0: Off
1: On
-
0: Off
Indicates whether a specific digital output (1…4) is ON or OFF.
When DO1 is ON, the bridge health status is OK. See also the parameter
"Bridge A/B HW system OK" under the "Bridge I/O" tab.
When DO2 is ON, the Generator commander has established a communication
connection to the selected bridge. See also the parameter "Bridge A/B
communication OK" under the "Bridge I/O" tab.
Bridge
A DO3
(a long list of
various inputs
and outputs)
-
-
This digital output can be customized according to the user's requirements.
Bridge
A DO4
(a long list of
various inputs
and outputs)
-
-
This digital output can be customized according to the user's requirements.
6.2.3 Remote and local control
Remote control
Table. 6.2.3 - 379. Control into excitation.
Name
Range
Step
Default
Description
Require
permission
to remote
control
0: No
1: Yes
-
0: No
When the Generator commander is controlled
remotely, this parameter defines whether a digital
input or the bus signal (enabled in the "Command
excitation to remote control" parameter below) is
also required for bus control.
When "No" is selected, the commander is in bus
control when controlled remotely.
Command
excitation to
remote
control
0: Off
1: On
-
0: Off
Activates and deactivates the remote bus controls.
See also the parameter "Require permission to
remote control" above.
Command
AVR
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the AVR control mode can
be controlled remotely.
Command
FCR
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the FCR control mode can
be controlled remotely.
Command
MVAR
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the MVar control mode can
be controlled remotely.
Command
PF (remote)
0: Off
1: On
-
0: Off
Selects whether or not the PF control mode can be
controlled remotely.
Unload Q
(remote)
0: Off
1: On
-
0: Off
Selects whether or not the reactive power can be
set to zero remotely.
Genera